Multi-drop Multiplexer (bus/string) - TC2900
Quick Product Search:
TC2900
Multi-Drop Fiber Optic Multiplexer (Bus/String: RS232/422/485)
Designed for Bus or String topologies, the TC2900 Multi-Drop Fiber Optic Multiplexer interconnects up to 12 Remote Terminal Units (RTU's) or Programmable Logic Controllers (PLC's) in Utility substation & SCADA networks requiring multiple channels. It is also used for similar connectivity applications in Traffic Control, Industrial Process and Security System networks.
The TC2900 works in "poll-response" (also called Slave/Master) types of communication networks. RS-232 and RS-485 interfaces are independent and operate over single mode or multimode fiber.
It is available with multiple masters for maximum reliability. Fault conditions are detected both Tx and Rx, upstream & downstream of each unit, and automatically re-route data paths to maintain network integrity. Dry contact alarms can be connected to RTUs/PLCs for pinpointing fault locations.
Features
- Bus or String Topologies
- Async Data Rates up to 38.4 Kbps
- Separate Broadcast & Respond Chls
- Multimode & Single Mode (850/1300/1550nm)
- Distances up to 100km
- 8 or 12 Channels RS-232/422/485
- Tx & Rx LEDs for Each Channel
- Anti-Streaming Capability
- Built-In Power Redundancy
- Local Dry Contact Alarm Relay
- Rackmount or Standalone
Applications
Designed for Bus or String topologies, the TC2900 is often used to interconnect Remote Terminal Units (RTUs) or Programmable Logic Controllers (PLCs) in Utility substation SCADA Networks that require multiple channels. It is also used for similar connectivity applications in Traffic Control, Industrial Process Control and Security System fiber optic networks.
Specifications
Data Rates
- Async RS-232/422/485to 38.4 Kbps
Optical
- TransmitterLED/ELED/LASER*
- ReceiverPIN Diode
- Wavelength850/1300nm Multimode, 1300/1550nm Single Mode
- Fiber Optic ConnectorsST or FC
- Loss Budget * - 850/1300/1550nm
- Multimode @62.5/125µm15dB
- Single Mode @9/125µm20dB
Electrical
- ConnectorRJ11 Female
- Interface(DCE) RS-232, RS-422, or RS-485 (2 or 4-wire)
Diagnostic Functions
- Local & Remote Loopback, Signal Generator, Master/SlaveYes
Power
- Standard12VDC @ 800mA
- Optional24VDC, -48VDC, or 115/230VAC with Power Cube
System
- Bit Error Rate1 in 109 or Better
Alarm
- Dry ContactNormal OPEN
Visual Indicators
- System PWR A, PWR B, VccA, VccB
- Electrical SignalTx Rx (for each channel)
- Optic SignalTxA, RxA, TxB, RxB, SYNC-A, SYNC-B, LP-A, LP-B
- AlarmPWRA, PWRB, OPTIC, AST (TC2851 only)
Temperature
- Operating-10°C to 50°C
- Hi-Temp1 (optional)-20°C to 70°C
- Storage-40°C to 90°C
- Humidity95% non-condensing
Physical (Rackmount Unit)
- Height(6.71 cm) 2.6"
- Width(18.10 cm) 7.1"
- Depth(24.89 cm) 9.8"
- Weight(1.82 kg) 4 lbs
* Contact factory for higher requirements